BLOCKS OF POWER SUPPLIES FOR CASES õëôó
(Technical conditions 31.1-30175784-006-2001 á)
Blocks of power supplies BPt-143 and BPt-144 are designed for:
replacement of P41240í/1-P and P41240í/2-P power supplies blocks that worked out their life time;
installation in cases UKTS-VL.
- BPt-143 is structurally compatible with P41240í/1-P
- BPt-144 is structurally compatible with P41240í/2-P
- BPt-143, BPt-144 surpass analogues in electric, reliability and weight parameters
- In BPt-143 there is no output voltage dependence of the "-15V" channel from settings of the output voltage and load current of the channel "+15V" (as distinct from P41240M/1-P)
- BPt-143, BPt-144 are installed into cases SB1 ÷ SB4 UKTS-VL.
- BPt-143 is installed into cases SRT1 ÷ SRT4 UKTS-VL
|
|
|
BPt-145 and BPt-146 have same electric parameters, as well as blocks BPt-143 and BPt-144, but for all that have smaller weight and dimension
Blocks of power supplies BPt-145, BPt-146 are designed for installation in cases UKTS-VL:
- BPt-145 and BPt-146 are installed into SHB5÷SHB4 UKTS-VL;
- BPt-145 is installed into SRT5÷SRT8 UKTS-VL;
|
|
|
COMPARISON CHARACTERISTICS OF POWER SUPPLIES BLOCKS
parameter
|
P41240í/1-P
|
BPt-143 (BPt-145)
|
P41240í/2-P
|
BPt-144 (BPt-146)
|
Channels
|
Channels
|
The channel
|
Channels
|
+15 V
|
-15 V
|
+15 V
|
-15 V
|
+24 V
|
+24 V
|
1.Output voltageat rating values of input voltage, load current and ambient air temperature of 25±10 C0, V
|
15±0,15
|
15±0,6
|
15±0,15
|
15±0,15
|
24±0,24
|
24±0,24
|
2.Load current, A:
- Nominal
- Maximal
- Minimal
|
8,0
9,0
0,5
|
4,0
4,5
0,05
|
8,0
9,0
0
|
4,0
4,5
0
|
6,0
8,0
0,1
|
6,0
8,0
0
|
3.Pulsation of output voltage (double amplitude), %, not more than
|
2,0
|
2,0
|
1,0
|
1,0
|
2,0
|
1,0
|
4. Total instability of output voltage (taking into account instability of input voltage, current, temperature), %, not more than
|
9,0
|
13,0
|
4,0
|
4,0
|
9,0
|
4,0
|
5. Operation threshold of current overload protection at the output of the block, A, within
|
9,5 - 12,5
|
5 - 8
|
10,0 - 12,5
|
5,5 - 8,0
|
8 - 12
|
9,0 - 12,0
|
6. Performance factor, %
|
65
|
80
|
56
|
80
|
7. Network filter availability
|
No
|
Yes
|
No
|
Yes
|
8. Nanosecond and microsecond antijamming availability
|
No
|
Yes
|
No
|
Yes
|
9. Electric strength of isolation, kV
Input - ground
Input - output
|
1,5
1,5
|
2,1
4,2
|
1,5
1,5
|
2,1
4,2
|
10. Operation temperature, C, within
|
+5 - +55
|
+5 - +60
|
+5 - +55
|
+5 - +60
|
11. Average mean-time between failures, h
|
50000
|
250000
|
50000
|
250000
|
12. Weight, kg, not more than
|
5,0
|
3,0 (1,5)
|
5,0
|
2,5 (1,5)
|
13. Average life time, years
|
10
|
30
|
10
|
30
|
14. Probability of fire occurrence, 1/year
|
10-6
|
10-8
|
10-6
|
10-8
|
|
|